Dear Fábio Oliveira, The feature you asked is possible. To configure this feature, please do the following steps: - open our ezManager sofware and - click "Search All" button to find CIE-H10 on your network - click on the product name to connect ezManager to product - do as shown on the attached image - click save button to save the configuration Thank you, Best regard, > Fábio Oliveira wrote: > ------------------------------------ > Good afternoon, > > I would like to know if it is possible to configure the CIE-H10 to do the following: > > 1. A normal connection is made in Modbus/TCP with the module. > 2. Some outputs are activated; > 3. Suddenly, the cable information is disconnected or some other line issue breaks the connection between the PC program and the module. > 4. All the outputs should be deactivated. > > I cannot make the module to put all outputs off when there is no connection. I can put all outputs off when I normally disconnect from the module ( I checked the box "Initialize the output port state" in the ez TCP manager). > > So, is there a way to make all the outputs off if the connection is abnormally lost? > > Thank you very much.