Dear Nathan Ward, Thank you for the inquiry. We would like to clarify if we understand your scenario correctly. Do you want to use CIE-M10 to control an output, upon getting the input signal from an alarm system? If so, you can refer to the answer below. To use input on CIE-M10 to trigger an output port, you can use the Macro function. This mode lets users set the values of the output ports using signals from other input/output ports on a CIE-M10. You can refer to page 31, CIE-M10 User Manual about the description and how to configure it via ezManager. https://www.eztcp.com/en/download/pds_files/ciem10aen.pdf For the pin assignments and operation voltage, you can refer to page 11, CIE-M10 User Manual. 1. For Input port: - Low state: +) Min VIL= -0.3V +) Max VIL= 0.8V - High State +) Min VIH= 2.0V +) Max VIH= 5.5V 2. For Output Ports: - Low state: +) Min VOH = 2.9V - High State +) Max VOL = 0.4V Thank you very much. Best Regards > Nathan Ward wrote: > ------------------------------------ > Hey, I want to connect a alarm system to the CIE-M10 inputs to change state on a fault. How do i wire that? I have a N/C to Common relay. Thanks for your help in advance