Name
E-mail
Company Name
Subject
Contents
Dear Customer, Thank you for the inquiry. Based on the information you provided, we suspect that the biasing resistors may be missing from the TRX+ and TRX- lines of the RS485. Please check that the biasing resistors are present and properly connected. TRX+ need to be pull-up and TRX- needs to be pull-down. Best Regards, > Sharon D wrote: > ------------------------------------ > Dear Sollae Support, We have recently aquired the CSEM53G Module and implemented it in our design (see attached). The module functions as so: We send a message in Ethernet we get a proper response from the Rs485 client however, on the 4th or 5th attempt the the response is distorted and displays a "" on every second note (see image attached). In the Image attached you will see 3 requests ("000200000ee8") and 3 proper response and on the 4th attempt we get a message with a "" on every second note. Please advise on the matter. Best