> Steffen wrote: > ------------------------------------ > Hallo, can see the status of the inputs / outputs via Modbus/TCP in the Macro mode (read only) thank you > Sollae Systems wrote: > ------------------------------------ > Hello, > > When using the Macro mode, you can't control the output ports of CIE-H10 with Modbus/TCP. > In that situation, the ouput ports can be controlled by only the macro function. > This option can be called stand alone operation. > To use this, you should know about the operaters "*", "+" and "/". > Each input ports can be a term of the simple formula based on boolean algebra. > Please refer to the manual to find how to use them. > > In the conclusion, when you use the macro mode, it doesn't allowed to controlling output ports via Modbus/TCP or HTTP. > > Have a nice day! > > > sam wrote: > > ~~~~~~~~~~~~~~~~~~~~~~~~~~~ > > Hy, > > I would like to know, how to use the macro mode? > > I try to run with macro's case option in "ezTCP manager.exe". But when i check this case, i can't send a modbus message whith another software. > > > > Thanks for your answer. > > Sam