한국어
|
English
PRODUCTS
SOLUTIONS
APPLICATIONS
SUPPORT
DOWNLOAD
WHERE TO BUY
ABOUT US
Support
>
Technical Support
Q&A
/ Technical Support
Name
E-mail
Company Name
Subject
Contents
> Harry wrote: > ------------------------------------ > Hello, What is the purpose of selecting macro function for each channel individually ? Is it possible for not Macro selected channels to be controlled by Modbus/TCP and HTTP ?? best regards Harry > Steffen wrote: > ------------------------------------ > > Hi, > > This is great :-) Thank you very much for answering my question. > > best Regarts > Steffen > > > Sollae Systems wrote: > > ------------------------------------ > > Hello. > > > > Of course it is possible to read the status of digital I/O ports even in the Macro mode via Modbus/TCP. > > > > Just controlling output ports are not possible in both ways. > > > > Thank you. > > > > > > > Steffen wrote: > > > ------------------------------------ > > > Hallo, > > > can see the status of the inputs / outputs via Modbus/TCP in the Macro mode (read only) > > > thank you > > > > > > > Sollae Systems wrote: > > > > ------------------------------------ > > > > Hello, > > > > > > > > When using the Macro mode, you can't control the output ports of CIE-H10 with Modbus/TCP. > > > > In that situation, the ouput ports can be controlled by only the macro function. > > > > This option can be called stand alone operation. > > > > To use this, you should know about the operaters "*", "+" and "/". > > > > Each input ports can be a term of the simple formula based on boolean algebra. > > > > Please refer to the manual to find how to use them. > > > > > > > > In the conclusion, when you use the macro mode, it doesn't allowed to controlling output ports via Modbus/TCP or HTTP. > > > > > > > > Have a nice day! > > > > > > > > > sam wrote: > > > > > ~~~~~~~~~~~~~~~~~~~~~~~~~~~ > > > > > Hy, > > > > > I would like to know, how to use the macro mode? > > > > > I try to run with macro's case option in "ezTCP manager.exe". But when i check this case, i can't send a modbus message whith another software. > > > > > > > > > > Thanks for your answer. > > > > > Sam
Password
Security Code
Attachment
(Image, ZIP file under 2MB)
Notice
Technical Support
FAQ
Q&A
Customer Support
Sales & Quotation
Survey