한국어
|
English
PRODUCTS
SOLUTIONS
APPLICATIONS
SUPPORT
DOWNLOAD
WHERE TO BUY
ABOUT US
Support
>
Technical Support
Q&A
/ Technical Support
Name
E-mail
Company Name
Subject
Contents
> Sharon D wrote: > ------------------------------------ > Dear Sollae Support, We have recently aquired the CSEM53G Module and implemented it in our design (see attached). The module functions as so: We send a message in Ethernet we get a proper response from the Rs485 client however, on the 4th or 5th attempt the the response is distorted and displays a "" on every second note (see image attached). In the Image attached you will see 3 requests ("000200000ee8") and 3 proper response and on the 4th attempt we get a message with a "" on every second note. Please advise on the matter. Best
Password
Security Code
Attachment
(Image, ZIP file under 2MB)
Notice
Technical Support
FAQ
Q&A
Customer Support
Sales & Quotation
Survey