No. 1206 Re: Re: macro to CIE-H10 2013-07-11

Hallo,
can see the status of the inputs / outputs via Modbus/TCP in the Macro mode (read only)
thank you

> Sollae Systems wrote:
> ------------------------------------
> Hello,
>
> When using the Macro mode, you can't control the output ports of CIE-H10 with Modbus/TCP.
> In that situation, the ouput ports can be controlled by only the macro function.
> This option can be called stand alone operation.
> To use this, you should know about the operaters "*", "+" and "/".
> Each input ports can be a term of the simple formula based on boolean algebra.
> Please refer to the manual to find how to use them.
>
> In the conclusion, when you use the macro mode, it doesn't allowed to controlling output ports via Modbus/TCP or HTTP.
>
> Have a nice day!
>
> > sam wrote:
> > ~~~~~~~~~~~~~~~~~~~~~~~~~~~
> > Hy,
> > I would like to know, how to use the macro mode?
> > I try to run with macro's case option in "ezTCP manager.exe". But when i check this case, i can't send a modbus message whith another software.
> >
> > Thanks for your answer.
> > Sam

Writer Steffen Company