No. 1207 Re: Re: Re: macro to CIE-H10 2013-07-11

Hello.

Of course it is possible to read the status of digital I/O ports even in the Macro mode via Modbus/TCP.

Just controlling output ports are not possible in both ways.

Thank you.


> Steffen wrote:
> ------------------------------------
> Hallo,
> can see the status of the inputs / outputs via Modbus/TCP in the Macro mode (read only)
> thank you
>
> > Sollae Systems wrote:
> > ------------------------------------
> > Hello,
> >
> > When using the Macro mode, you can't control the output ports of CIE-H10 with Modbus/TCP.
> > In that situation, the ouput ports can be controlled by only the macro function.
> > This option can be called stand alone operation.
> > To use this, you should know about the operaters "*", "+" and "/".
> > Each input ports can be a term of the simple formula based on boolean algebra.
> > Please refer to the manual to find how to use them.
> >
> > In the conclusion, when you use the macro mode, it doesn't allowed to controlling output ports via Modbus/TCP or HTTP.
> >
> > Have a nice day!
> >
> > > sam wrote:
> > > ~~~~~~~~~~~~~~~~~~~~~~~~~~~
> > > Hy,
> > > I would like to know, how to use the macro mode?
> > > I try to run with macro's case option in "ezTCP manager.exe". But when i check this case, i can't send a modbus message whith another software.
> > >
> > > Thanks for your answer.
> > > Sam

Writer Sollae Systems Company