No. 1207 | Re: Re: Re: macro to CIE-H10 | 2013-07-11 | ||
---|---|---|---|---|
Hello. Of course it is possible to read the status of digital I/O ports even in the Macro mode via Modbus/TCP. Just controlling output ports are not possible in both ways. Thank you. > Steffen wrote: > ------------------------------------ > Hallo, > can see the status of the inputs / outputs via Modbus/TCP in the Macro mode (read only) > thank you > > > Sollae Systems wrote: > > ------------------------------------ > > Hello, > > > > When using the Macro mode, you can't control the output ports of CIE-H10 with Modbus/TCP. > > In that situation, the ouput ports can be controlled by only the macro function. > > This option can be called stand alone operation. > > To use this, you should know about the operaters "*", "+" and "/". > > Each input ports can be a term of the simple formula based on boolean algebra. > > Please refer to the manual to find how to use them. > > > > In the conclusion, when you use the macro mode, it doesn't allowed to controlling output ports via Modbus/TCP or HTTP. > > > > Have a nice day! > > > > > sam wrote: > > > ~~~~~~~~~~~~~~~~~~~~~~~~~~~ > > > Hy, > > > I would like to know, how to use the macro mode? > > > I try to run with macro's case option in "ezTCP manager.exe". But when i check this case, i can't send a modbus message whith another software. > > > > > > Thanks for your answer. > > > Sam |
Writer | Sollae Systems | Company | |
|
|||