No. 1225 Re: Re: Re: Re: Re: Re: macro to CIE-H10 2013-10-07

Hello,

Yes, you are right.

You can choose a controlling function for each channel.

If you choose Macro for one of channels then the channel only uses Macro.

If you don't choose Macro then you can control the channle through Modbus/TCP or HTTP.

Thank you.


> Harry wrote:
> ------------------------------------
> Hello,
>
> What is the purpose of selecting macro function for each channel individually ?
> Is it possible for not Macro selected channels to be controlled by Modbus/TCP and HTTP ??
>
> best regards
> Harry
>
> > Steffen wrote:
> > ------------------------------------
> >
> > Hi,
> >
> > This is great :-) Thank you very much for answering my question.
> >
> > best Regarts
> > Steffen
> >
> > > Sollae Systems wrote:
> > > ------------------------------------
> > > Hello.
> > >
> > > Of course it is possible to read the status of digital I/O ports even in the Macro mode via Modbus/TCP.
> > >
> > > Just controlling output ports are not possible in both ways.
> > >
> > > Thank you.
> > >
> > >
> > > > Steffen wrote:
> > > > ------------------------------------
> > > > Hallo,
> > > > can see the status of the inputs / outputs via Modbus/TCP in the Macro mode (read only)
> > > > thank you
> > > >
> > > > > Sollae Systems wrote:
> > > > > ------------------------------------
> > > > > Hello,
> > > > >
> > > > > When using the Macro mode, you can't control the output ports of CIE-H10 with Modbus/TCP.
> > > > > In that situation, the ouput ports can be controlled by only the macro function.
> > > > > This option can be called stand alone operation.
> > > > > To use this, you should know about the operaters "*", "+" and "/".
> > > > > Each input ports can be a term of the simple formula based on boolean algebra.
> > > > > Please refer to the manual to find how to use them.
> > > > >
> > > > > In the conclusion, when you use the macro mode, it doesn't allowed to controlling output ports via Modbus/TCP or HTTP.
> > > > >
> > > > > Have a nice day!
> > > > >
> > > > > > sam wrote:
> > > > > > ~~~~~~~~~~~~~~~~~~~~~~~~~~~
> > > > > > Hy,
> > > > > > I would like to know, how to use the macro mode?
> > > > > > I try to run with macro's case option in "ezTCP manager.exe". But when i check this case, i can't send a modbus message whith another software.
> > > > > >
> > > > > > Thanks for your answer.
> > > > > > Sam