No. 1432 | Re: Re: Re: CSE-H53 baud rate | 2016-11-14 | ||
---|---|---|---|---|
I tested it and it works! Thanks, Joep > joep wrote: > ------------------------------------ > Thanks! > > Indeed Telnet COM Port Control was turned on. > I'm not in the opportunity to test this until the weekend so I'll post an update after that. > > Joep > > > > Sollae Systems wrote: > > ------------------------------------ > > Dear Joep, > > > > Thank you for using our products. > > The CSE-H53 isn'st support telnet commands for the settings. > > You can change the settings of the com port on ezTCP manager. > > I think you check an option about Telnet COM Port Control(RFC2217) in Serial Port tab. > > If the option is enable you can'st control the settings of the com port. > > Please try again after you turn off the option. > > > > Thank you. > > > > > > > joep wrote: > > > ------------------------------------ > > > I have a CSE-H53 with a Sony beamer connected on the RS-232 port. > > > This beamer requires a baud rate of 38.4 kbps with even parity, one stop and one start bit. > > > I would like to send a command to the RS-232 port with telnet from a linux machine. > > > I can successfully connect to the CSE-H53 with telnet. > > > For example 'sst uptime's works fine. > > > > > > I cannot find any way to set the baud rate and the other settings of the com port. > > > I tried ezTCP manager 3.5C on a Windows machine but the options for CPM1 are all greyed out. > > > > > > Do you have any idea how to do this? > > > Thanks, > > > Joep |
Writer | joep | Company | |
|
|||