No. 1432 Re: Re: Re: CSE-H53 baud rate 2016-11-14

I tested it and it works!

Thanks,
Joep


> joep wrote:
> ------------------------------------
> Thanks!
>
> Indeed Telnet COM Port Control was turned on.
> I'm not in the opportunity to test this until the weekend so I'll post an update after that.
>
> Joep
>
>
> > Sollae Systems wrote:
> > ------------------------------------
> > Dear Joep,
> >
> > Thank you for using our products.
> > The CSE-H53 isn'st support telnet commands for the settings.
> > You can change the settings of the com port on ezTCP manager.
> > I think you check an option about Telnet COM Port Control(RFC2217) in Serial Port tab.
> > If the option is enable you can'st control the settings of the com port.
> > Please try again after you turn off the option.
> >
> > Thank you.
> >
> >
> > > joep wrote:
> > > ------------------------------------
> > > I have a CSE-H53 with a Sony beamer connected on the RS-232 port.
> > > This beamer requires a baud rate of 38.4 kbps with even parity, one stop and one start bit.
> > > I would like to send a command to the RS-232 port with telnet from a linux machine.
> > > I can successfully connect to the CSE-H53 with telnet.
> > > For example 'sst uptime's works fine.
> > >
> > > I cannot find any way to set the baud rate and the other settings of the com port.
> > > I tried ezTCP manager 3.5C on a Windows machine but the options for CPM1 are all greyed out.
> > >
> > > Do you have any idea how to do this?
> > > Thanks,
> > > Joep