No. 1463 Re: CIE-H10 + CIE-H12 2017-01-06

Dear Carlos Tadeo,

It’s possible to setup your system with CIE-H10 and CIE-H12.

I am not so clear about your systems, so I categorize in two case:
- Only one input port of CIE-H10 controls all of six CIE-H12
- Six input ports of CIE-H10 controls all of six CIE-H12 (each input control one device)
The second case will become the first case if parameters of six CIE-H12 are set the same. So, I will explain the second case.

We called this system is “Internet Switch”,. Please refer to the following:
- Introduction: http://www.eztcp.com/en/applications/internet_switch.php
- Demonstration: https://www.youtube.com/watch?v=JRFxd1mkun0
- Document: http://www.eztcp.com/documents/application/an_internet_switch_en.pdf
- Example setting: http://www.eztcp.com/documents/application/an_comb_iocontrollers_en.pdf (In your case, refer to page 5 and 6)
- Configuration logic: If CIE-H10 and CIE-H12 is configured as the attached file ( with 0 <= n <= 7 , 8<= m <=15)
I explain configuration logic through a data transaction between CIE-H10 and CIE-H12.
To make explanation simple, I simplify the transaction between CIE-H10 and CIE-H12. Irrelated steps are ignored.

CIE-H12 as master request:
- Request to read nth-address input port of CIE-H10 (slave)
- Read its own input port (2 ports) and request to write these values to mth and (m+1)th-address outputs port of CIE-H10
CIE-H10 handles the request and send the response:
- Set its mth and (m+1)th-address output ports according to values from the request
- Read its own nth-address input port and send it to CIE-H12
CIE-12 handle response:
- Set its output port to value from the response

Note 1:
- Address of input ports of CIE-H10 are from 0 to 7.
- Address of output ports of CIE-H10 are from 8 to 15
Note 2:
- If you only use one-direction control (Input port of CIE-H10 control output port of CIE-H12), maximum topology is 1:8 (1 CIE-H10 controls 8 CIE-H12). In this case, Input ports of CIE-H12 and output port of CIE-H10 should not be used.
- If you use two-direction control (Input ports of CIE-H10 control output port of CIE-H12, Input ports of CIE-H12 control output port of CIE-H10), maximum topology is 1:4 (1 CIE-H10, 8 CIE-H12. The example setting shows this case.

Note 3:
- Use can combine the first case and second case (as mentioned at the beginning), but maximum CIE-H18 is 8 per a CIE-H10 because CIE-H10 only allow maximum 8 Modbus/TCP connections.



> Carlos Tadeo wrote:
> ------------------------------------
> Hi Guys,
>
> We need to configure the equipment CIE-H10 with 6 remote cie-h12 model to use relay outputs activated by a h10 input, is this possible? And how could we do it?
>
> Your representantive in Mexico just send us a manual, but i can´t do the link betwen both equipments, so i suspect that CIE-H10 is damaged but i want make more test because we are interested on integrate this solution in other projects, so we need understand the configuration logic
>
> Thanks a lot.
>
> PS. I allready have read the manuals

Attachment 20170106_img.png
Writer Sollae Systems Company