No. 1497 | Re: Re: Desactivate Outputs if no connection | 2017-05-16 | ||
---|---|---|---|---|
That is a very good news. I initially used that option, but as I didn't wait one minute I never saw the ports going back to the initial state. I will use this. Thank you very much for your support!! > Sollae Systems wrote: > ------------------------------------ > In previous reply, I show how to configure the feature you want. > > It'ss worth to note that, if that option is enable, output port is set to initial state when TCP connection is closed. > > If you manually close the TCP connection in the software, output port will be initialized immediately. > > In case the cable connection is lost, it takes about one minute to detect TCP connection is closed. Therefore, it takes about one minute before initializing. > > Thank you, > > Best regard, > > > Fábio Oliveira wrote: > > ------------------------------------ > > Good afternoon, > > > > I would like to know if it is possible to configure the CIE-H10 to do the following: > > > > 1. A normal connection is made in Modbus/TCP with the module. > > 2. Some outputs are activated; > > 3. Suddenly, the cable information is disconnected or some other line issue breaks the connection between the PC program and the module. > > 4. All the outputs should be deactivated. > > > > I cannot make the module to put all outputs off when there is no connection. I can put all outputs off when I normally disconnect from the module ( I checked the box "Initialize the output port state" in the ez TCP manager). > > > > So, is there a way to make all the outputs off if the connection is abnormally lost? > > > > Thank you very much. |
Writer | Fabio | Company | Electronica Industrial |
|
|||