No. 1516 Re: Re: Re: Re: CSE-H55N2 Client - server configuration BACnet MS/TP 2017-09-01


Thanks.

1: IP conflict: Already checked, but will check again.
2: I use the same type of power source as for my MODbus configuration, and already placed a stronger power supply
3: I'll test this with another cable.

I've tested that the client looses connection, ethernet cable can be the issue.
Also i connected the devices with a RS485 cable direct, and connection stays stable.

As soon as i have tested this, i'll let you know if it is fixed or not.

Thanks so far.



> Sollae Systems wrote:
> ------------------------------------
> Hello Ferry,
>
> Thank you for detail information.
>
> We checked your configuration on both devices and there is nothing wrong with these configurations. There are some possible reasons which make your system work unstably.
> 1. IP address is conflicted with IP of another device.
> 2. Power source us unstable and it could make CSE-H55N2 reset and then the connection will be lost and re-established.
> 3. Ethernet cable is unstable, it could make the connection lost
>
> Could you please check these above reasons?
>
> If the problem is not solved, please feel free to contact us!
>
> Best regards,
>
>
> > ferry wrote:
> > ------------------------------------
> >
> > Hello again,
> >
> > In the attachment you find the 2 configuration exports.
> >
> > When i look in the state in EZ manager, normally the state is "connection established"
> >
> > When my BACnet device is offline in the controller, the state is "connection lost" (or something). a few minutes later the connection is back. and the communication is back.
> >
> > > Sollae Systems wrote:
> > > ------------------------------------
> > > Hello Ferry,
> > >
> > > Thank you for using our products.
> > >
> > > In order to find out the reason, we would like to ask some additional information.
> > >
> > > 1. Could you please describe more detail about your network topology (for example, PC <-> internet <-> CSE-H55N2 <-> BACnet MS/TP device ....)?
> > > 2. Could you please tell us how you detect that connection is lost ?
> > > 3. Could you please send us the configuration files of both CSE-H55N2 device (on ezManager software, go to "Advanced Menu" -> Export Variables -> save file and send us)
> > >
> > > Thank you,
> > >
> > > Best regards,
> > >
> > >
> > > > Ferry wrote:
> > > > ------------------------------------
> > > > Hi,
> > > >
> > > > On a site i have 1 BACnet MS/TP device, running over a server-client configuration with 2 CSE-H55N2's.
> > > >
> > > > ~ 4-6 times a day the conection between the two devices get lost.
> > > > On the same plant i have the same configuration with MODbus RTU, works fine.
> > > >
> > > > The only different is the protocol and the baudrate.
> > > > Modbus is running on 9600 with parity even, Bacnet is running on 19K2 without parity.
> > > >
> > > > Do i need to do a special setting in the H55N2's?