No. 1626 Re: Re: Re: Re: Re: Re: Re: Re: Re: Re: Connection with Mitsubishi L-serie 2019-01-19

Hello,
In the future we are going to use the CSE-H21 with the Mitsubishi FX-serie, with the official programming cable, with RS232 connection (no mini-USB), because that works well.
The project below, where it didn't work well (L-serie with mini-USB or ethernet), we solved it with another industrial VPN router.

Thanks for helping us.


> Sollae Systems wrote:
> ------------------------------------
> Dear Johan,
>
> Thank you for your information.
> Based on your information, it is possible that the problem lies in serial connection.
> If you have any RS-232 to USB cable, you can also try to directly connect your PLC to a PC, to check if it is micro USB to RS-232 cable problem or not.
> Any standard cable without defect should work well with CSE-H21.
>
> Note that there are two COM ports on CSE-H21, so you should also make sure that ezVSP and your PLC connect to the same serial port of CSE-H21 (COM1/COM2), otherwise, it won't work.
> For example, if you use serial port COM1 of CSE-H21, according to your setting parameters, the virtual COM port on ezVSP should be configured as:
> + TCP Client
> + Host IP: 192.168.1.50
> + Host Port: 1470
>
> Please feel free to contact us if the problem still persists.
> Thank you very much.
> Best Regards,
>
> > Johan wrote:
> > ------------------------------------
> > Hello,
> >
> > "If it only has serial interface to connect to CSE-H21, you need to use ezVSP"
> > reaction: Yes we did
> >
> > I still think the mini USB cable is our problem, because in the past we used the same configuration,see QA1611 with a Mitsubishi FX-serie, in combination with the standard Mitsubishi programming cable(SC09 RS232-RS422), without any problem.
> > Do you think you can advise us a converter(cable), DB9 female to USB mini ?
> >
> >
> >
> > > Sollae Systems wrote:
> > > ------------------------------------
> > > Dear Johan,
> > >
> > > Thank you for your information.
> > > However, we still need more information of your working scheme to make it clear about your issue.
> > >
> > > It is clear that you can connect your PC with CSE-H21 via ezManager for configuration.
> > > However, it is still unclear for us that how your PC connected to CSE-H21 in the working scheme.
> > > Could you please let us know how exactly did CSE-H21 connect to your PC in that case?
> > >
> > > We suppose that you are trying to connect CSE-H21 to the same software that you previously used to connect your PC to your PLC.
> > > (As mentioned in our previous reply https://www.eztcp.com/en/support/qna_view.php?bbs_id=3&page=1&cid=161)
> > > Is it correct? If so, how did you configure your software to connect it to CSE-H21?
> > >
> > > If your software has TCP/IP interface to connect to CSE-H21, you can configure the connection interface on your software with the IP and port number of CSE-H21 device.
> > > If it only has serial interface to connect to CSE-H21, you need to use ezVSP.
> > >
> > > And please make sure the serial interface between your PLC and your CSE-H21 is properly set on your PLC.
> > >
> > > Maybe we can establish a remote support session via TeamViewer for further analysis?
> > > Thank you very much for your understanding.
> > > Best Regards,
> > >
> > >
> > > > Johan wrote:
> > > > ------------------------------------
> > > >
> > > > New attachment
> > > >
> > > > > Sollae Systems wrote:
> > > > > ------------------------------------
> > > > > Dear Johan,
> > > > >
> > > > > We are sorry we can not open the attachment.
> > > > > We got error message every time we try.
> > > > > Could you please check again to see if there is an error with your attachment?
> > > > >
> > > > > Thank you very much.
> > > > > Best Regards,
> > > > >
> > > > >
> > > > > > Johan wrote:
> > > > > > ------------------------------------
> > > > > > Good Morning,
> > > > > >
> > > > > > The connection settings
> > > > > >
> > > > > > Thanks for your fast respons
> > > > > >
> > > > > >
> > > > > > > Sollae Systems wrote:
> > > > > > > ------------------------------------
> > > > > > > Dear Johan Lindeboom,
> > > > > > >
> > > > > > > Yes, the problem may be in the USB cable.
> > > > > > > However, for further analysis, we still need more information about connection setting on each device in your working scheme.
> > > > > > >
> > > > > > > If possible, we can establish a TeamViewer session.
> > > > > > > You can set up a schedule and send your credentials (ID and password) to us via email support@eztcp.com.
> > > > > > > Our working time is from 9:00 to 18:00 in UTC+9 Time zone.
> > > > > > > Thank you for your understanding.
> > > > > > > Best Regards
> > > > > > >
> > > > > > >
> > > > > > > > Johan wrote:
> > > > > > > > ------------------------------------
> > > > > > > > Good afternoon again,
> > > > > > > >
> > > > > > > > The state of the problem is,
> > > > > > > > * Connection of the PC with the CSE-H21 (remote connected)is OK
> > > > > > > > * Question: Can the USB Cabel from CSE-H21 to PLC L-serie be the problem (serial RS232/USB mini)
> > > > > > > >
> > > > > > > > Johan Lindeboom
> > > > > > > >
> > > > > > > >
> > > > > > > > > Sollae Systems wrote:
> > > > > > > > > ------------------------------------
> > > > > > > > > Dear Johan Lindeboom,
> > > > > > > > >
> > > > > > > > > Thank you for being our valued customer.
> > > > > > > > >
> > > > > > > > > As we understand, the connection should be like this:
> > > > > > > > > PC <-- TCP/IP --> CSE-H21 <-- Serial --> PLC.
> > > > > > > > >
> > > > > > > > > To find out whether the problem happens in TCP/IP connection or in Serial connection, we would like to ask for more information.
> > > > > > > > >
> > > > > > > > > First, please make sure the serial configuration is set properly between the PLC and CSE-H21 device.
> > > > > > > > >
> > > > > > > > > There will be a TCP/IP connection between CSE-H21 and your PC.
> > > > > > > > > We guess that your working scheme is similar to the one in the attached photo below.
> > > > > > > > > (You are trying to connect CSE-H21 to the same serial software on your PC that you used to connect to PLC device previously)
> > > > > > > > >
> > > > > > > > > In that case, you may need to use ezVSP to connect CSE-H21 and your software on your PC. https://www.eztcp.com/en/download/ezvsp.php
> > > > > > > > > ezVSP is a virtual serial port driver and TCP/IP socket program, distributed for free by Sollae Systems. (ezVSP User Manual: https://www.eztcp.com/en/download/pds_files/an_ezvsp_en.pdf)
> > > > > > > > >
> > > > > > > > > If you still can not find any problem with your setting, could you please send us the screenshot of Serial and TCP/IP setting on your CSE-H21, and also let us know the configuration for the interface in your PC/your PLC with CSE-H21?
> > > > > > > > >
> > > > > > > > > Thank you very much for your understanding.
> > > > > > > > > Best Regards,
> > > > > > > > >
> > > > > > > > >
> > > > > > > > >
> > > > > > > > > > Johan Lindeboom wrote:
> > > > > > > > > > ------------------------------------
> > > > > > > > > > Hello,
> > > > > > > > > >
> > > > > > > > > > I have a problem to connect a Mitsubishi PLC, type L02, to a CSE H21.
> > > > > > > > > > The WAN connection online is ok.
> > > > > > > > > >
> > > > > > > > > >
> > > > > > > > > >
> > > > > > > > > >
> > > > > > > > > > Former configuration with a Mitsubishi F-serie gave no problem. The PLC was then coupled using the official progamming cable (RS422)

Writer Johan Company