No. 1885 Re: Etherenet to Rs485 failure 2023-04-21

Dear Customer,

Thank you for the inquiry.

Based on the information you provided, we suspect that the biasing resistors may be missing from the TRX+ and TRX- lines of the RS485.
Please check that the biasing resistors are present and properly connected.
TRX+ need to be pull-up and TRX- needs to be pull-down.

Best Regards,


> Sharon D wrote:
> ------------------------------------
> Dear Sollae Support,
We have recently aquired the CSEM53G Module and implemented it in our design (see attached).
The module functions as so: We send a message in Ethernet we get a proper response from the Rs485 client however, on the 4th or 5th attempt the the response is distorted and displays a "" on every second note (see image attached).
In the Image attached you will see 3 requests ("000200000ee8") and 3 proper response and on the 4th attempt we get a message with a "" on every second note.
Please advise on the matter.